Output Signal
Pneumatic on/off or proportional pressure
signal
Ranges:
Throttling: 0.2 to 1.0 bar (3 to 15 psig) or 0.4 to
2.0 bar (6 to 30 psig)
On/Off: 0 (off) or full supply pressure (on)
Action: Field-reversible between direct (increasing
level increases output signal) and reverse (increasing
level decreases output signal)
Supply Pressure Requirements
Throttling Controller:
Throttling: 1.4 bar (20 psig) for 0.2 to 1.0 bar (3 to 15
psig) output signal and 2.4 bar (35 psig) for 0.4 to 2.0
bar (6 to 30 psig) output signal
On/Off: Any desired pressure between 1.4 and 3.4 bar
(20 and 50 psig)
Cutting Oil